Skip to main content

Water hammer — causes, math, prevention

Water hammer is a transient pressure spike from sudden valve closure. The Joukowsky equation, critical closure time, column separation, and proven fixes.

Published Updated by Pipe Flow Lab Editorial

Close a valve too quickly and the water column behind it — moving at 6 ft/s through a copper main — cannot stop instantly. Mass times velocity has to go somewhere. It converts into a pressure wave that travels back along the pipe at roughly the speed of sound in water, slams the upstream boundary, and reflects. Each reflection rattles the pipe, stresses every joint, and on a bad day drives a pinhole through a soldered tee. That is water hammer — formally a hydraulic transient in the language of fluid mechanics, and the single most common cause of fittings failure in residential and commercial water systems.

This guide covers the physics in two equations, why the Joukowsky equation occasionally underpredicts the spike, the six mechanisms that cause hammer, the symptoms engineers see in the field, the codes that mandate arresters, and how to spec a ASSE 1010-rated arrester correctly. Everything is referenced to authoritative sources — Crane Technical Paper 410, ASPE Plumbing Engineering Design Handbook, AWWA M11, ASME B31.3, IPC 2024, and PDI WH-201.

The 30-second version: Water hammer pressure rise ΔP = ρ · a · Δv. For water in copper at 2 m/s that is ~380 psi above static — well over the 150 psi soldered-joint rating. Fix it by slowing closures past 2L/a, designing under 2.4 m/s, and installing ASSE 1010 arresters per PDI WH-201 fixture-unit tables.

The pressure wave, animated

When a downstream valve slams shut, the fluid layer touching the valve stops first. The layer behind it stops a fraction of a millisecond later. The "stopped" boundary moves backward as a compression wave at the wave speed a (≈ 1,400 m/s in water, 4,600 ft/s). Watch the red front travel left through the pipe, bounce off the source as a low-pressure reflection, and return toward the valve. One full round trip equals 4L/a; the audible knock typically lasts several round trips before friction dissipates the wave.

ReservoirValve+ΔP surge−ΔP rarefactionWave speed a ≈ 1,400 m/s in water · Period = 4L/a
One full cycle: compression wave travels upstream, reflects as a rarefaction, returns. Each round trip equals 4L/a; the wave damps over 3-10 cycles.

The three regimes of a pipe transient

Not every flow change is a Joukowsky event. Engineering practice distinguishes three regimes by how fast the deceleration happens relative to the pipe geometry:

  1. Rigid column (slow transient). Closure time greater than ~5L/a. The water column decelerates as one mass; pressure rise is moderate and given by ΔP ≈ ρ · L · (dv/dt). This is the regime hydraulic textbooks treat as "quasi-steady." A 10-second motor-operated gate valve on a 60 m line behaves this way.
  2. Elastic transient (intermediate). Closure between 2L/a and ~5L/a. Pressure rise is less than Joukowsky but more than rigid-column; engineers interpolate linearly between the two as a conservative estimate.
  3. Full Joukowsky surge (fast transient). Closure faster than 2L/a. The first reflected wave has not returned before the valve has fully shut; the fluid column has no escape and the spike reaches the full Joukowsky value. Solenoid valves, fast-acting pressure-reducing valves, and pump trips all sit in this regime.

The two equations you actually need

Joukowsky surge. For instantaneous valve closure, the peak pressure rise above line static is:

ΔP = ρ · a · Δv

where ρ is fluid density (1,000 kg/m³ for water at 20 °C), a is the wave speed in the pipe (depends on pipe stiffness — see Korteweg below), and Δv is the change in fluid velocity. For water at 2 m/s in copper, that is 1000 × 1310 × 2 = 2.62 MPa ≈ 380 psi on top of the static line pressure. Standard 80 psi domestic systems are not rated for that, and neither are most quarter-turn ball valves (typically 600 psi static but much lower dynamic rating).

Critical closure time. Joukowsky-magnitude only occurs if the valve closes faster than one full wave round trip:

tc = 2L / a

For a 60 m pipe run in copper, tc ≈ 0.09 s. Closure slower than this gives the fluid time to decelerate gradually — the surge magnitude drops roughly linearly with closure time once you pass tc. This is the entire reason quick-closing solenoid valves on washing-machine hoses are a problem and slow-close gate valves are not. Specifying tclose > 5·tc (the rigid-column regime) is the cheapest guaranteed fix.

Surge magnitude scales linearly with velocity

Double the design velocity and you double the spike. The bar chart below shows Joukowsky pressure rise for water in copper at 1, 2, and 3 m/s — the third bar is the reason ASPE caps domestic cold-water velocity at ~2.4 m/s and hot water at ~1.5 m/s in the Plumbing Engineering Design Handbook.

0200400600ΔP (psi)80 psi (typical domestic)v = 1 m/s190 psiv = 2 m/s380 psiv = 3 m/s570 psiJoukowsky surge — water in copper, instant closure
Surge magnitude is linear in velocity. At 3 m/s the spike is 7× the static rating of a typical domestic line.

Wave speed is set by the pipe, not just the fluid

If pipes were perfectly rigid the wave speed would equal the speed of sound in the bulk fluid (1,480 m/s for water at 20 °C). Real pipes flex slightly under the pressure pulse, which slows the wave. The correction is the Korteweg formula:

a = √( (K/ρ) / (1 + (K · D) / (E · e)) )

K is fluid bulk modulus (~2.2 GPa for water), D is inside diameter, E is the pipe's Young's modulus, and e is the wall thickness. The takeaway is in the table — soft plastics absorb a lot of the surge, steel and copper barely any.

Wave speed in water-filled pipes (1″ schedule, 20 °C)
E (GPa)a (m/s)Joukowsky at 2 m/s
Rigid limit (theoretical)1,4802.96 MPa / 430 psi
Steel, schedule 402001,3602.72 MPa / 395 psi
Copper, type L1101,3102.62 MPa / 380 psi
Ductile iron1701,3302.66 MPa / 385 psi
PVC, schedule 802.85401.08 MPa / 157 psi
HDPE SDR 110.83200.64 MPa / 93 psi
PEX0.62900.58 MPa / 84 psi

This is one of the underrated reasons PEX is the dominant residential material now — the wave speed is roughly a quarter of copper's, so the surge for the same flow change is also roughly a quarter. Soldered copper systems in old buildings hammer audibly; PEX systems with the same fixtures usually do not. It does not eliminate the need for arresters — IPC §604.9 still requires them at quick-close fixtures — but it does reduce risk of joint fatigue.

When Joukowsky underpredicts: column separation

The Joukowsky equation assumes the water column stays intact. In real systems with sloping pipes, pump trips, or any negative-pressure excursion, the local pressure can drop to the vapor pressure of water (~2.3 kPa absolute at 20 °C). At that point liquid water flashes to vapor; a vapor cavity forms; the upstream and downstream water columns separate. When downstream pressure rises again, the cavity collapses and the two columns rejoin at high relative velocity — and the resulting collision pulse can reach roughly three times the Joukowsky value, with experimental cases reported up to two orders of magnitude above reservoir static pressure (Bergant & Simpson, "Water hammer with column separation," 2006).

Column separation is the single biggest reason a hand calculation can underpredict a real transient. Any system with the following characteristics should be analysed with a Method-of-Characteristics solver, not by Joukowsky alone:

  • Long sloping mains where the hydraulic grade line can dip below the pipe elevation
  • Pump-trip scenarios on critical service (firewater, chilled-water, irrigation mains)
  • Systems with check valves placed far from the pump (sets up a long reverse-flow column)
  • Cold-water systems where vapor pressure is reached before line pressure compensates

The six mechanisms that cause water hammer

"Valve closure" gets the most press but is only one of six recognised triggers. Designing against hammer means designing against the worst-case mechanism in your system, which is rarely a valve.

  1. Quick-closing valve. Solenoid valves on dishwashers, washing machines, and modern smart faucets close in 5-25 ms — orders of magnitude faster than the critical closure time of any realistic residential pipe run. This is the dominant residential cause and the one IPC §604.9 explicitly targets.
  2. Pump trip. When a pump loses power, the discharge stops driving forward flow. The water downstream of the pump continues by inertia, leaves a low-pressure void at the pump, and may flash to vapor (see column separation above). When the column reverses, it slams the check valve. The transient is often worse than valve-closure hammer because flow reverses through a closed boundary.
  3. Pump start against closed discharge. Centrifugal pumps started with a closed discharge valve develop full shutoff head almost instantaneously; opening the valve then releases that high-pressure column into the downstream pipe as a pulse. Standard procedure is to start with the discharge cracked open or to spec a soft-start VFD.
  4. Check-valve slam. Swing-type check valves slam shut when forward flow stops and reverse flow develops. The slam itself is a fast closure event. Use silent (spring-assisted) check valves on pump discharges to avoid this; standard swing-check K ≈ 2 carries an unpredictable additional dynamic load.
  5. Column-separation cavity collapse. Discussed in detail above — the rejoining of separated water columns can exceed Joukowsky predictions by 2-3×.
  6. Air pocket compression. Trapped air at a high point compresses under any downstream surge, then explosively re-expands when the surge passes. Vent air at every high point with combination air-release / air-vacuum valves on long mains.

How to recognise water hammer in the field

Hammer events leave specific signatures. Diagnosing it correctly matters because the fixes for hammer differ from the fixes for cavitation, pump surge, or simple pipe-vibration problems that sound similar.

  • Audible knock or bang on valve closure. Sharp single bang or a rapid series of 3-10 bangs immediately after a valve closes — never during steady flow. The sound is the pipe deflecting against its hangers, not the fluid making noise.
  • Visible pipe movement. Exposed pipe (basements, mechanical rooms) physically jumps under hammer. If you can see and time the jump to a fixture closing upstairs, you have confirmed the source.
  • Recurring leaks at fittings. Pinhole or weeping leaks at soldered tees, threaded fittings, or flange faces — particularly if leaks recur after repair at the same locations — are the signature of repeated surge cycling.
  • Pressure-gauge spikes. A datalogged gauge (or pressure-recording valve such as a Watts USG-A installed at a hose bib for 24 hours) captures spikes of 100-400 psi lasting 50-200 ms in hammer-affected systems. Healthy systems stay within ±20 psi of static.
  • Pump or motor wear signatures. Repeated pump-trip hammer accelerates seal failure, shaft fatigue, and impeller damage on the suction side. Pumps that fail at 30% of rated life on otherwise clean water are usually hammer victims.

Prevention: the engineering toolbox

Open air chamber (legacy)Air springWaterfixtureASSE 1010 bladder arresterSealed gasBladderfixturesurge in
Both devices buy you time. Open air chambers waterlog as the trapped air dissolves into the water column; ASSE 1010 bladder arresters are sealed and do not waterlog. Modern codes require ASSE 1010 devices.

Once you have identified hammer, the engineering response is one or more of the following. The order matters — do the cheapest thing first.

  1. Slow the closure. Replace quarter-turn ball valves with gate valves on critical lines; spec lever-actuated valves with closure dampers; require closure time greater than 5L/a on automated valves. Free if specified at design time. Solves most hammer problems on its own.
  2. Reduce the design velocity. Joukowsky is linear in Δv. Going from 2.4 m/s to 1.5 m/s cuts the surge by ~40%. Use the velocity calculator to check before specifying pipe sizes; if velocity is already in the safe band, surge magnitude is survivable for short events.
  3. Install ASSE 1010 water-hammer arresters at every quick-close fixture. ASSE 1010 devices are factory-sealed bladder or piston arresters tested to keep the surge pressure below 150 psi when subjected to a standardised 400 psi spike. They are required by IPC §604.9 wherever quick-closing valves are installed.
  4. Spec silent check valves on pump discharges. Spring-assisted "silent" check valves close on the velocity decay before reverse flow develops, eliminating the slam pulse.
  5. Use VFD soft-start and controlled-stop ramps on pumps. A 5-10 second acceleration ramp keeps pump-start hammer in the rigid-column regime; a controlled deceleration ramp does the same for normal shutdown.
  6. Surge tanks and expansion tanks on long mains. For municipal water mains, fire-protection systems, and industrial transfer lines, a properly sized surge tank or diaphragm-type bladder accumulator at the critical point absorbs the wave at scale.

Sizing arresters: PDI WH-201 fixture-unit method

PDI WH-201 is the industry standard for sizing water-hammer arresters by fixture-unit count, used throughout commercial plumbing design. Total the fixture units served by the branch line and pick the corresponding size:

PDI WH-201 arrester sizing by fixture units
Fixture unitsTypical use
PDI Size A1 – 11Single fixture (one solenoid)
PDI Size B12 – 32Small branch — kitchen + adjacent bath
PDI Size C33 – 60Floor branch — small commercial restroom
PDI Size D61 – 113Riser — small multi-floor building
PDI Size E114 – 154Riser — mid-rise commercial
PDI Size F155 – 330Main riser — high-rise / institutional

Place the arrester within 6 ft (2 m) of the quick-closing valve and on the same branch — locating it back at the main does not protect the fixture from the local surge. Mount in any orientation (modern bladder units are position-independent) and ahead of the shutoff so the device is always pressurised.

Codes and standards engineers should know

Hammer prevention is governed by multiple overlapping standards. The minimum-compliance set for commercial work in the U.S. is:

  • IPC §604.9 (2024). "The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer's instructions and shall conform to ASSE 1010."
  • ASSE 1010 (2021). Performance and certification standard for water-hammer arresters. Devices must withstand 150 psi static, operate from 0 to 60 psi line pressure, function at 33 °F to 180 °F, and during the endurance test reduce a 400 psi spike to below 150 psi without failure.
  • PDI WH-201 (2017). Plumbing & Drainage Institute fixture-unit sizing method (Size A through F) for selecting arresters on branch lines.
  • ASPE Plumbing Engineering Design Handbook, Vol. 4. Source for the velocity bands (cold water 5-8 ft/s, hot water 3-5 ft/s) that designers use to keep surge magnitudes survivable in the first place.
  • AWWA M11. Steel Pipe — A Guide for Design and Installation; contains the definitive treatment of surge analysis on municipal mains.
  • ASME B31.3 / B31.9. Process Piping and Building Services Piping. The relevant pressure-design rules; transient pressures up to 33% above design are typically allowed for short events but anything beyond requires explicit surge analysis.

Software for transient analysis

For systems where Joukowsky underpredicts — long sloping mains, pump-trip scenarios, networks with significant column-separation risk — a full transient analysis is required. The standard commercial packages all solve the governing equations using the Method of Characteristics (MOC), which converts the partial-differential continuity and momentum equations into a pair of ordinary differential equations along characteristic lines in the x-t plane.

  • AFT Impulse (now Datacor Impulse) — MOC-based, integrates with AutoPIPE; common in nuclear, petrochemical, and large water-utility work.
  • Bentley HAMMER — bundled with the Bentley OpenFlows water-utility suite; widely used for municipal water analysis.
  • KYPipe Surge — wave-form theory implementation; the original from the University of Kentucky.
  • PIPENET Transient — Sunrise Systems; common in firewater and offshore work.
  • Add-ons for CAESAR II and AutoPIPE for combined stress / transient checks.

Rule of thumb: if your system has any of the column-separation risk factors above, or contains a critical-service pump, or has total length over 500 m on a single main, do a full MOC analysis rather than relying on a Joukowsky hand calculation.

Worked examples

Example 1 — Kitchen solenoid hammer

System: 60 m of ½″ copper at 2 m/s feeding a dishwasher solenoid that closes in ~10 ms.    Critical closure time: 2 × 60 / 1310 = 0.092 s = 92 ms.    Surge: closure is 9× faster than critical → full Joukowsky → 1000 × 1310 × 2 = 2.62 MPa ≈ 380 psi on top of the 60 psi static line → 440 psi peak.

Copper Type L is rated to ~700 psi cold so the pipe wall survives, but soldered joints fatigue and the fixture rating (typically 150 psi) is wildly exceeded. The fix here is one PDI Size A, ASSE 1010 bladder arrester at the fixture branch (the dishwasher is < 11 fixture units). Install within 6 ft of the solenoid, ahead of the shutoff valve.

Example 2 — Pump trip on a chilled-water riser

System: 80 m vertical chilled-water riser, 3″ steel, 1.8 m/s design velocity, 60 kW centrifugal pump losing power on a campus brownout.    Joukowsky bound: 1000 × 1360 × 1.8 ≈ 2.45 MPa ≈ 355 psi.    Column separation risk: the riser drops below the hydraulic grade line within seconds of pump trip; vapor cavity forms near the top floor.

Joukowsky alone is not conservative — cavity collapse can multiply the spike. This system requires (a) a Method-of-Characteristics analysis, (b) a silent check valve at the pump, (c) a bladder accumulator at the riser top, and (d) controlled-deceleration VFD shutdown on planned stops to eliminate the trip scenario. Without all four, expect main-rupture risk.

Example 3 — Irrigation lateral quick-close

System: 150 m of 2″ PVC schedule 80 lateral, 1.5 m/s, electrically actuated ball valve closing in 1 s.    Critical closure time: 2 × 150 / 540 = 0.56 s.    Regime: closure is 1.8× critical — elastic transient, not full Joukowsky. Expected surge ~60% of ρ · a · Δv0.6 × 1000 × 540 × 1.5 ≈ 486 kPa ≈ 70 psi on top of the 50 psi static → 120 psi peak.

PVC Sch 80 in 2″ is rated to ~400 psi, well above the spike. No arrester required if the closure time stays at 1 second; specifying a faster valve (a manual quarter-turn closing in < 0.3 s) would push the system into the Joukowsky regime and require either a slower actuator or a surge-relief valve.

Rule of thumb: design under 2.4 m/s, spec slow-close valves on automated lines, install PDI-sized ASSE 1010 arresters at every quick-close fixture, and do a Method-of-Characteristics analysis any time pump trip or column separation is plausible. Hammer becomes a non-issue.

Where water hammer matters most

The fix list is generic, but the priority is industry-specific:

  • Residential plumbing. Solenoid-valve hammer at washing machines and dishwashers dominates; one PDI Size A arrester per appliance solves most cases. PEX systems have lower surge per event but still need arresters at solenoids per IPC §604.9.
  • Commercial and high-rise. Riser arresters sized per PDI table (Size E/F at main risers, Size D at floor branches). VFD soft-start required on booster pumps; silent check valves on every pump discharge.
  • Fire-protection systems. Standpipes and sprinkler risers see pump-start hammer at every test cycle. NFPA 14 requires arresters at the highest hose connection; spec ASSE 1010 rated for the static-pressure class of the riser.
  • Irrigation. Long PVC laterals with electrically actuated valves; the soft wave speed in PVC keeps surges modest if closure stays above critical. Quick-close manual valves are the failure mode.
  • HVAC hydronic. Chilled-water and condenser-water loops with multiple variable-speed pumps are exposed to pump-trip hammer; column separation is the dominant risk and a transient analysis is standard for systems above 50 kW pump load.
  • District energy and municipal water mains. Surge analysis per AWWA M11 is mandatory; surge tanks at strategic high points; controlled valve actuation across the network.

FAQ

What is water hammer in plumbing?

Water hammer is a transient pressure spike that travels through a piping system when flowing water is forced to stop or change direction abruptly. Closing a valve quickly converts the kinetic energy of the moving water column into a pressure pulse that propagates upstream at roughly the speed of sound in water (≈ 1,400 m/s). The pulse rattles fittings, fatigues joints, and produces the characteristic banging noise.

What causes water hammer?

The most common triggers are quick-closing solenoid valves on dishwashers and washing machines, sudden pump trips on power loss, pump starts against a closed discharge valve, check-valve slam when flow reverses, vapor-cavity collapse after column separation, and trapped air pockets that compress under surge. Modern fixtures with electronic shutoff have made the problem more frequent because they close faster than the critical closure time of most residential pipe runs.

How do you stop water hammer?

Three engineering fixes work, in order of cost. First, slow down the closure: replace quarter-turn ball valves with gate valves on critical lines and spec slow-stroke actuators where automation is required. Second, reduce the design velocity below ASPE recommended bands (2.4 m/s cold water, 1.5 m/s hot). Third, install an ASSE 1010-rated water-hammer arrester at every quick-close fixture, sized by PDI WH-201 fixture-unit tables.

Is water hammer dangerous?

Yes — and it gets more dangerous the longer it is ignored. A single Joukowsky surge on a domestic copper line can reach 380 psi on top of static pressure, well above the 125-150 psi rating of soldered fittings and typical fixture rough-ins. Even when nothing fails on the first event, repeated hammering fatigues solder joints and gasket faces, and column-separation events can produce instantaneous pressures up to roughly three times Joukowsky predictions. Documented failures range from pinhole leaks to catastrophic main rupture.

Can water hammer break pipes?

Yes. The pipe wall itself usually survives a single event (copper Type L is rated to ~700 psi cold), but the failure points are soldered joints, threaded fittings, fixture connection rough-ins, gasketed flange faces, and any branch with a partially seized valve. The most common visible failure is a pinhole or split at a soldered tee or 90° elbow. In severe column-separation events, even ductile-iron mains can rupture.

What does water hammer sound like?

A sharp single bang or a rapid series of bangs immediately after a valve closes — never during steady flow. The sound is the pipe physically deflecting against its hangers or studwork as the pressure wave passes; it is not the fluid itself making noise. A "gurgling" or "humming" sound is something different (usually air entrainment or cavitation). Well-clamped pipe can transmit a 300 psi spike silently, which is more dangerous because the joint fatigue is still happening.

Do PEX pipes get water hammer?

Yes, but the surge magnitude is roughly a quarter of copper or steel for the same flow change. PEX has a low Young's modulus (~0.6 GPa), so the Korteweg-corrected wave speed in PEX is about 290 m/s versus 1,310 m/s in copper. The Joukowsky pressure rise is proportional to wave speed, so PEX systems hammer less audibly. PEX still needs arresters at solenoid-valve fixtures per IPC §604.9.

Why does my water hammer get worse over time?

Almost always because the air chambers above the affected fixtures have waterlogged. The trapped air in an open-style air chamber slowly dissolves into the water column over weeks to months, and once the air spring is gone the surge transmits straight to the fixture. The fix is either to recharge the chambers (shut off main, drain, refill) or replace them with sealed-bladder ASSE 1010 arresters, which do not waterlog.

How do you diagnose water hammer?

Identify the fixture and the moment: hammer occurs when something closes, not when it opens or runs. Use a dataloggable pressure gauge (or a pressure-recording valve like the Watts USG-A) installed at a hose bib for 24 hours to capture surge events; healthy systems stay within ±20 psi of static, hammer systems show spikes of 100-400 psi lasting 50-200 ms. Knock that synchronises with a specific appliance shutoff confirms the source.

Is the Joukowsky equation always accurate?

No. Joukowsky predicts the surge for instantaneous valve closure assuming no column separation and a rigid wave-speed assumption. In real systems with sloping pipes, pump trips, or any negative-pressure excursion, the fluid can vaporise locally and form a vapor cavity. When that cavity collapses and the separated water columns rejoin, the resulting pressure can reach roughly three times the Joukowsky value (and in extreme experimental cases more). For pump-trip-induced transients on long mains, a full Method-of-Characteristics analysis is required.

How long does water hammer last?

A single surge cycle is one round trip of the pressure wave: t = 4L/a, where L is the distance to the next reservoir or significant elasticity and a is the wave speed. For a 60 m copper run, that is about 0.18 seconds. The audible knock typically dies out after 3-10 cycles as friction and acoustic radiation damp the wave, so the total noise event is around 0.5-2 seconds.

Do pressure-reducing valves cause water hammer?

They can both mask and cause it. A PRV lowers the upstream velocity which reduces the Joukowsky surge for downstream events, but a fast-acting PRV closing in response to a sudden demand spike can itself be a hammer source. Specify a PRV with a controlled stroke time greater than 2L/a of the supply main, and install a downstream expansion tank to absorb the residual pulse.

Sources and further reading

  • Joukowsky, N. E. (1898). "Über den hydraulischen Stoss in Wasserleitungsröhren." Original treatment of the surge equation.
  • Crane Company, Technical Paper 410: Flow of Fluids through Valves, Fittings, and Pipe. Pressure-loss reference and transient guidance.
  • ASPE, Plumbing Engineering Design Handbook, Vol. 4. Velocity bands, fixture units, and arrester selection.
  • AWWA, M11 — Steel Pipe: A Guide for Design and Installation. Surge analysis for water mains.
  • ASME B31.3 / B31.9. Pressure-design rules including transient allowances.
  • PDI WH-201 (2017). Water hammer arrester certification and sizing.
  • ASSE 1010 (2021). Performance requirements for water hammer arresters.
  • IPC 2024, §604.9. Code requirement for arresters at quick-closing valves.
  • Bergant, A. & Simpson, A. R. (2006). "Water hammer with column separation: A historical review." Journal of Hydraulic Research.
  • ASHRAE Handbook 2021, Chapter 22 (Pipe Sizing). Friction-factor and roughness data.

Open the tools